Technical guide · Power cables · YJV & VV

YJV and VV are the fixed power cables that carry electricity from a distribution board to the load — through a building, a plant or a yard, in a trench, a duct or a conduit. Both are built to GB/T12706-2008 for 0.6/1 kV fixed power distribution. The difference is the insulation: YJV uses cross-linked polyethylene (XLPE) and runs at 90 °C, VV uses PVC and runs at 70 °C. Our cable selector lists 8,985 standard power-cable constructions in this family — YJV and VV and their armoured, flexible, shielded, flame-retardant and low-smoke sisters. This guide explains the whole family: how to read a model code, what each member is, and which one fits your feeder.

YJV and VV power cables

1. What YJV and VV are

The build is a fixed power cable to the factory’s published data: copper conductors, XLPE insulation on YJV and PVC insulation on VV, and a PVC sheath — YJY is the same XLPE cable with a PE sheath instead of PVC. Rated voltage is 0.6/1 kV, the power-frequency test is 3.5 kV for 5 minutes, and the laying temperature must not fall below 0 °C (preheat the cable if it does). The cable is made for transmitting and distributing power at 0.6/1 kV — the feeder from a board to a machine, a pump, a lighting circuit or a building riser — laid fixed indoors, in cable trenches, in ducts or in conduit. Our power cable range lists the whole family, and the selector below it lists every size — 8,985 standard constructions across seven sub-groups, 1–5 cores × 1.5–400 mm².

YJV is the standard fixed power cable, and VV is its PVC sister. If the run has to move, the family has flexible members for that (YJVR, VVR); if the power run needs screening, there are shielded members (YJVP, VVRP, YJVRP); if the run needs mechanical protection, there are armoured members (YJV22, VV22). Picking the wrong member is the most common mistake in power cabling: a stiff YJV forced to flex will crack at the gland, and an unshielded power run beside a drive will put noise into the control lines running next to it. The rest of this guide is about telling the members apart before you order.

8,985 standard constructions: YJV series 3,973 + VV series 3,225 + WDZ series 1,127 + aluminium conductor 189 + aluminium alloy conductor 189 + mining 162 + special 62 armour 120. Every one of them is listed in our cable selector with its stock code, construction, outer diameter and weight — the numbers in this guide are recomputed from that selector, not from a catalogue summary.

2. How to read a YJV / VV model code

The model names are construction codes. Each letter adds one fact about the build:

Code partMeaningWhat it tells you
YJCross-linked polyethylene (XLPE) insulationThe insulation that sets YJV apart from VV
VPVC insulationFirst V: the insulation on each core (VV, VVR)
VPVC sheathSecond V: the outer sheath (YJV, VV)
YPE sheathSecond Y: a polyethylene outer sheath (YJY)
RFlexible buildSofter construction for moving runs (YJVR, VVR)
PBraided shieldCopper braid screen around the cores (YJVP, VVRP, YJVRP)
LAluminium conductorAluminium instead of copper (YJLV)
HAlloyAluminium-alloy conductor, with L (YJLHV)
MMiningMining power cable (MVV, MYJV)
22Steel-tape armourArmoured build for mechanical protection (YJV22, VV22)
23Suffix — confirm construction on enquiryListed in our selector; the factory material does not publish what this suffix builds
62Armour suffix — confirm construction on enquiryListed as special 62 armour, single-core only
ZR- / ZC- / ZA-Flame-retardant prefixSame size grid as the base model, flame-retardant sheath
WDZ-Low-smoke zero-halogen flame-retardant prefixLow-smoke zero-halogen insulation and sheath
NH-Fire-resistant prefixFire-resistant build, same size grid (NH-YJV)
ZRN- / ZCN-Flame-retardant + fire-resistant prefixCombined prefix (ZRN-YJV, ZCN-YJV)

So YJV is XLPE-insulated with a PVC sheath, VV is PVC-insulated with a PVC sheath, and YJY is XLPE-insulated with a PE sheath. R makes it flexible, P adds a braided shield, L swaps the copper for aluminium, and 22 adds steel-tape armour. Once you can read it, you can read the whole range.

TypeConstruction differenceCarriesChoose it when
YJVXLPE insulation, PVC sheath, fixed.Fixed power distribution at 0.6/1 kVThe standard fixed feeder — board to load, trench, duct or conduit.
VVPVC insulation, PVC sheath, fixed.The same job in PVCThe specification calls for PVC, or the PVC build fits the budget.
YJVR / VVRFlexible versions of YJV / VV.Power to runs that move or are re-terminatedThe run moves or is handled often; a stiff cable would fatigue at the gland.
YJVP / VVRP / YJVRPAdds a braided shield.Power beside drives and control linesThe run needs screening — a drive next door puts noise into everything around it.
YJV22 / VV22Steel-tape armour over the fixed build.Feeders in trenches, ducts and exposed runsThe cable can be crushed or struck — the armour, not the sheath, takes the blow.
WDZ-YJY / WDZA-YJY / WDZN-YJYLow-smoke zero-halogen build.Power where low smoke mattersPublic buildings and escape routes — ask us to confirm the WDZ class for your project.
NH-YJV / ZRN-YJVFire-resistant build.Power circuits that must keep working in a fireThe circuit is safety-critical; ask us to confirm the fire rating for your project.
YJLV / YJLHVAluminium / aluminium-alloy conductor.The same feeders, far lighterWeight matters on a long run — confirm the termination with us.
MVV / MYJVMining builds.Mining power3–4 cores × 1.5–300 mm², built for mining use.
23 / 62 buildsSuffix — confirm construction on enquiry.Listed sizes, construction to confirmAsk us before ordering — the factory material does not publish the build.

3. The family in numbers

All seven sub-groups, with selector counts and outer-diameter ranges recomputed from our data. Each base model lists 129 sizes: an 81-size main grid — 1–5 cores × 1.5–400 mm², with 400 mm² only as a single core — plus 48 sizes with a smaller additional core (3+1, 3+2 and 4+1). The armoured 22 and 23 models list 112 sizes: a 64-size main grid (2–5 cores × 1.5–300 mm²) plus the same 48. The counts below count selector rows and the spec ranges show the distinct size grid.

Sub-groupConstructionSelector rowsSpec rangeOuter diameter
YJV seriesXLPE insulation3,9731–5 cores × 1.5–400 mm²5.6–88.0 mm
VV seriesPVC insulation3,2251–5 cores × 1.5–400 mm²5.8–91.0 mm
WDZ seriesLow-smoke zero-halogen XLPE1,1271–5 cores × 1.5–400 mm²5.6–88.0 mm
Aluminium conductorXLPE, aluminium conductor1891–5 cores × 10–400 mm²8.1–87.7 mm
Aluminium alloy conductorXLPE, aluminium-alloy conductor1891–5 cores × 10–400 mm²8.1–87.7 mm
MiningMVV / MYJV1623–4 cores × 1.5–300 mm²10.1–65.2 mm
Special 62 armourSingle-core armoured1201 core × 10–300 mm²11.7–33.0 mm

Two things stand out. First, the shielded and armoured members run larger at the same size — compare YJV 3 cores × 50 mm² with YJV22 3 cores × 50 mm² in the worked rows below: the armour adds millimetres, and the gland and conduit must be sized from the exact row, never from the base model. Second, the national-standard and full-section series share the same outer diameter at the same size — the full-section build simply carries more copper, so it weighs more: YJVR 3 cores × 50 mm² is 1,732 kg/km in the national-standard series and 1,822 kg/km full-section; VVR 3 cores × 50 mm² is 1,897 kg/km against 1,986 kg/km. If your specification calls for full-section conductors, say so in the enquiry — the model code alone does not tell us which series you want.

4. YJV vs VV

The two base models share a voltage, a standard, a test and a bend rule. The insulation is what differs — and it is the whole difference:

RatingYJV (XLPE)VV (PVC)
InsulationCross-linked polyethylene (XLPE)PVC
Conductor long-term working temperature90 °C70 °C
Short-circuit temperature (max 5 s)180 °C160 °C up to 300 mm²; 140 °C above 300 mm²
Rated voltage U0/U0.6/1 kV0.6/1 kV
Power-frequency test3.5 kV / 5 min3.5 kV / 5 min
StandardGB/T12706-2008GB/T12706-2008
Laying temperatureNot below 0 °C (preheat below 0 °C)Not below 0 °C (preheat below 0 °C)
Minimum bend radius, single-core20× OD unarmoured; 15× OD armoured20× OD unarmoured; 15× OD armoured
Minimum bend radius, three-core15× OD unarmoured; 12× OD armoured15× OD unarmoured; 12× OD armoured

At the same size YJV is the smaller and lighter cable: 3 cores × 50 mm² is 26.0 mm outer diameter and 1,653 kg/km in YJV, against 28.0 mm and 1,791 kg/km in VV. The 90 °C rating is the reason YJV is the default for a fixed feeder — the same size runs hotter in YJV than in VV, so a VV feeder sized from a YJV habit will run closer to its limit. The flexible members differ from the fixed rule: VVR and VVRP list a 6×D bend radius for mobile installation and a −15 to +70 °C use temperature on their factory pages, while YJVR’s factory page repeats the fixed-cable bend rule (20×/15×/15×/12×) and the 70 °C long-term temperature — so size YJVR bends from the fixed-cable rule, not from 6×D. Flame-retardant builds (ZR-/ZC-/ZA-) pass the GB/T18380 bundle burning test, with smoke density to GB/T17651.1 and HCl release of no more than 100 mg/g; fire-resistant builds (NH-) meet GB/T12666. And one honest weight comparison for long runs: the aluminium-alloy YJLHV 3 cores × 95 mm² weighs 1,275 kg/km against 3,010 kg/km for copper YJV at the same size — but the conductor is aluminium alloy, so confirm the termination with us before ordering.

5. Worked example: bend radius and six real rows

The minimum bend radius is a multiple of the cable’s outer diameter, and the multiple depends on the build. The factory’s published rule: single-core cable, unarmoured 20× the outer diameter and armoured 15×; three-core cable, unarmoured 15× and armoured 12×; flexible VVR for mobile installation, 6×. Worked examples: YJV 3 cores × 50 mm² (E101030500003) has an outer diameter of 26.0 mm, so as a three-core unarmoured cable it must not be bent tighter than a 390.0 mm radius. YJV22 3 cores × 50 mm² (E101070500003) has an outer diameter of 29.0 mm, so as a three-core armoured cable its minimum radius is 348.0 mm. YJV 1 core × 120 mm² (E101031200001) has an outer diameter of 19.0 mm, so as a single-core unarmoured cable its minimum radius is 380.0 mm. VVR (national standard) 3 cores × 2.5 mm² (E102020025003) has an outer diameter of 12.0 mm, so as a flexible cable for mobile installation its minimum radius is 72.0 mm. The full method is in our guide to minimum bend radius for drag chain cables.

Six real stock sizes from our cable selector — stock code, model, construction, outer diameter and weight:

Stock codeModelConstructionOuter dia.Weight
E101030500003YJV3×5026.0 mm1,653 kg/km
E101010500003VV3×5028.0 mm1,791 kg/km
E101070500003YJV223×5029.0 mm1,943 kg/km
E101031200001YJV1×12019.0 mm1,236 kg/km
E102020025003VVR (national standard)3×2.512.0 mm197 kg/km
E101090950003WDZ-YJY3×9534.0 mm3,010 kg/km

Weight is worth checking before you order a drum: YJV 3 cores × 50 mm² at 1,653 kg/km means 100 m weighs 165.3 kg. And one honest difference between the factory catalogue and our selector: the factory’s printed power-cable list covers only 1–5 cores × 1.5–70 mm² (marked partial, “page limited”), while our selector lists the full grid to 400 mm² shown above. Two small gaps in the data: VVR (national standard) lists 128 rows, not 129 — the 3×16+1×10 size is not listed, so ask us to confirm it; and ZC-YJV and ZC-VV list 127 rows each, with no 1×400, no 4×2.5+1×1.5 and no 5×300. Sizes outside the selector grid are made to order — send the specification and we will confirm availability.

6. How to choose

Your jobChooseWhy
Fixed feeder from board to loadYJVXLPE at 90 °C, the standard fixed power cable; smaller and lighter than VV at the same size.
Same feeder, PVC specifiedVVPVC at 70 °C; heavier and larger at the same size, so check the gland and the route.
Feeder to a moving machine partYJVR / VVRThe flexible build survives movement; VVR bends at 6×D for mobile installation.
Power beside a drive (VFD)YJVP / VVRP / YJVRPThe braided shield keeps drive noise out of the lines around it — see our guide to VFD 3+3 shielding.
Trench, duct or exposed run where the cable can be struck or crushedYJV22 / VV22Steel-tape armour takes the mechanical load; size the gland from the exact row, it runs larger than YJV.
Low-smoke requirementWDZ-YJYLow-smoke zero-halogen build — ask us to confirm the WDZ class for your project.
Circuit that must keep working in a fireNH-YJV / ZRN-YJVFire-resistant build on the same size grid — ask us to confirm the fire rating for your project.
Long run where weight mattersYJLV / YJLHVAluminium / aluminium-alloy conductor, far lighter than copper — confirm the termination with us.
Mining powerMVV / MYJV3–4 cores × 1.5–300 mm², built for mining use.
A 23 or 62 buildAsk usThe factory material does not publish the construction — confirm on enquiry before ordering.

Frequently asked questions

What is the difference between YJV and VV?
YJV is XLPE-insulated and VV is PVC-insulated — same 0.6/1 kV rating, same GB/T12706-2008 standard, same test and bend rule, but the conductor runs at 90 °C in YJV and 70 °C in VV. At the same size YJV is also smaller and lighter: 3 cores × 50 mm² is 26.0 mm and 1,653 kg/km in YJV, against 28.0 mm and 1,791 kg/km in VV.
What do the 22, 23 and 62 suffixes mean?
22 is steel-tape armour — the armoured build for trenches, ducts and exposed runs. For 23 and 62 the factory material publishes no construction: our selector lists WDZ-YJY23 and WDZN-YJY23 in 2–5 cores × 1.5–300 mm², and the 62 models as single-core 10–300 mm² only, but what the suffix builds is a question for enquiry, not a guess. Send the model and we will confirm the construction with the factory.
What sizes are actually in stock?
Each base model lists 129 sizes — an 81-size main grid of 1–5 cores × 1.5–400 mm², with 400 mm² only as a single core, plus 48 sizes with a smaller additional core (3+1, 3+2, 4+1). Across the family our selector lists 8,985 standard rows. The factory’s printed list is shorter (1–5 cores × 1.5–70 mm², marked partial); sizes outside the selector grid are made to order.
Can I use YJV or VV outdoors or buried?
Only the armoured members for runs that can take a mechanical blow: YJV22 and VV22 carry the steel-tape armour, with a 12× bend radius for three-core cable. Unarmoured YJV and VV are fixed cables — for a buried run, ask us to confirm, as no direct-burial rating is published in the factory material.
What if my size is not in the selector?
Send us the model, core count, conductor size and outer diameter you need — plus what the cable connects to, so we can confirm the construction. Custom builds start from 300 m, and we usually give a formal quote within one working day. See also our guide to custom cable assemblies made to drawing.

Send the model, core count and diameter

Send the YJV or VV model, core count and outer diameter — plus what the cable connects to, if you want us to confirm the insulation and shielding level. We confirm the construction and usually quote within one working day.