Technical guide · VFD and drive cables · EMC

A variable-frequency drive does not output clean sine-wave power. It outputs fast pulse trains, and everything downstream — common-mode currents, bearing wear, interference in neighbouring cables — follows from that. The motor cable is not an accessory to the EMC design; it is part of it. That is what the symmetric 3+3 construction is for.

What “3+3” means

A conventional four-core motor cable carries three phases plus one protective earth conductor tucked wherever it fits. A 3+3 VFD cable (our BPYJVP) splits the earth into three equal conductors placed symmetrically in the gaps between the three phase cores. The geometry is balanced: every phase sees the same capacitance to earth, the return paths share the same impedance, and high-frequency common-mode current gets a controlled, predictable route back to the drive instead of hunting for one through the machine frame and the motor bearings.

Selection pointConventional 4-coreSymmetric 3+3 shielded
Conductor layout3 phases + 1 earth, asymmetric3 phases + 3 earth conductors, evenly distributed
High-frequency return pathDepends on earth position and installationBalanced earths + shield provide a controlled path
EMC behaviourExtra mitigation often neededDesigned for low emissions when terminated correctly
Bearing-current contributionUncontrolled return paths raise the riskPart of the recognised mitigation strategy

Two shields, two jobs

BPYJVP carries a dual shield: an inner copper tape wrap giving continuous electrostatic coverage, and an outer copper wire braid (80% coverage density in our construction) that carries the high-frequency currents. Around them: XLPE insulation (low capacitance — every metre of cable adds capacitance the drive must charge at each switching edge, so this matters more as runs get longer) and a 0.6/1 kV rating with Class 5 flexible conductors.

Both shields only work if they are terminated over the full 360° at both ends — EMC gland or shield clamp at the drive cabinet and at the motor terminal box, unshielded tails kept as short as possible. A shield twisted into a pigtail is, at switching frequencies, barely a shield at all: it is the single most common VFD installation error, the same one that haunts servo cabling.

Installation rules for VFD runs

  • Keep the shield continuous — avoid joints; where one is unavoidable, maintain full-circumference shield continuity through the enclosure.
  • Separate the motor cable from signal and data runs; cross at right angles where crossing is unavoidable.
  • Do not use the shield as the protective earth — the 3+3 design has dedicated earth conductors; the shield is an EMC component.
  • Follow the drive manufacturer’s EMC instructions for gland plates and bonding — the cable completes that system, it does not replace it.
  • On long runs, account for cable capacitance and reflected-wave stress: low-capacitance XLPE construction helps, but permissible length still depends on the drive, switching frequency and motor insulation.

Our range: the cable selector publishes the standard BPYJVP 3+3 constructions with full diameter and weight data. Flexible (BPYJVRP) and other VFD constructions are built to specification — send the drive and motor data and we will match the construction.

Frequently asked questions

Can I feed a VFD motor with a normal 4-core cable?
People do, on small drives and short runs — and inherit the risks: radiated emissions, common-mode current through unintended paths, and bearing currents that quietly shorten motor life. Most drive manufacturers’ EMC instructions call for a shielded, symmetric cable; the larger the drive and the longer the run, the less optional it becomes.
Shield at one end or both ends?
Both ends, over 360°, for VFD duty. The shield is a high-frequency return path, not a signal screen on an audio cable; single-end termination defeats it at switching frequencies.
Does a 3+3 cable eliminate bearing currents?
No cable alone eliminates every bearing-current mechanism — shaft grounding and insulated bearings have their place on large motors. The symmetric shielded cable is the first, standard layer of mitigation and the one the drive makers specify.
What sizes are standard?
The selector lists the published BPYJVP constructions by core size with outside diameters. If your drive/motor combination needs a size or a flexible variant outside that table, it is a specification build — ask us with the drive data.

Matching a cable to a drive?

Send the drive model, motor rating and run length. We will confirm the 3+3 construction, the size, and whether the standard table covers it or it is a specification build.

VFD range in the selector Request a quote